Monicon CGS500 IR Datasheet
The CGS500-IR NDIR Gas Sensor is an infrared sensor designed to replace thermocatalytic (pellistor) gas sensors. It measures hydrocarbon gases in the range 0-100% LEL using miniaturised NDIR technology. The key benefit of the infrared technology is that it is not affected by catalytic poisons. It is certified ATEX II 2G EEx d IIC T6 and is available as a sensor only or fitted in an EEx e certified junction box.
| Specification | Value |
|---|---|
| ATEX Certification | II 2 G EExd IIC T6 (Certificate No. BAS00ATEX2246X) |
| Detection Range | 0-100% LEL |
| Operating Voltage & Current | 3.0Vdc @ 100mA |
| Operating Temperature Range | -20 degrees C to +40 degrees C |
| Repeatability | +/- 2% LEL CH4 at 20 degrees C |
| Drift | +/- 1% LEL CH4 per month at 20 degrees C |
| Sensor MTBF | 10 years |
| Mounting Thread | M25 X 1.5mm |
| Junction Box Size (Excl. Sensor) | W: 75mm, D: 58mm, H: 80mm |